Water System No. : DE0000552 Federal Type : C
Water System Name : ARTESIAN WATER COMPANY State Type : C
Principal County Served : NEW CASTLE Primary Source : SWP
Status : A Activity Date : 09-01-1977
Lab Sample No. : A07060707-AIP Collection Date : 06-13-2007
This list displays sample/results of all non-microbial analytes (TSAANLYT.TYPE_CODE <> MOR) associated to the selected sample. Results for Microbial Analytes are not included.

Analyte Code Analyte Name Method Code Less than Indicator Level Type Reporting Level Concentration level Monitoring Period Begin Date Monitoring Period End Date
1000 TOTAL CHLORINE null N MRL 0.01 MG/L 1.03  MG/L
1013 FREE RESIDUAL CHLORINE null N MRL 0.01 MG/L .87  MG/L
1016 CALCIUM 3500CA-D N MRL 1 MG/L 251  MG/L
1017 CHLORIDE null N MRL 0.39 MG/L 46.10  MG/L
1025 FLUORIDE null N MRL 0.02 MG/L .97  MG/L
1028 IRON null N MRL 0.004 MG/L .01  MG/L
1043 PHOSPHATE, TOTAL 4500H-B N MRL 0.03 MG/L .91  MG/L
1055 SULFATE 300.0 N MRL 0.38 MG/L 37  MG/L
1064 CONDUCTIVITY @ 25 C UMHOS/CM 2510B N 0 MG/L 1148  UMHO/CM
1901 CARBON DIOXIDE null N MRL 1 MG/L 12  MG/L
1905 COLOR 110.2 Y MRL 2 CT  CU
1915 HARDNESS, TOTAL (AS CACO3) null N MRL 1 MG/L 345  MG/L
1925 PH 4500H-B N 0 MG/L 7.55  PH
1927 ALKALINITY, TOTAL 2320B N MRL 1 MG/L 257  MG/L
1930 TDS 2510B N MRL 10 MG/L 430  MG/L
1996 TEMPERATURE (CENTIGRADE) null N 0 MG/L 17  C
1997 LANGELIER INDEX (PH(S)) null N MRL 0 MG/L .4  LANG

 

 


Total Number of Records Displayed = 17